Exchange HVAC Model (Equipment)
Exchange of information about shape, size and location of HVAC components.
HVAC systems information can then be brought together with equivalent information from other roles to ensure that items of equipment are in proper spatial and functional relationship to each other taking into account their size and location in terms of space allocation and structural provision.
Please ensure that you have read the process mapping document HVAC Engineering (PM) before proceeding with this exchange requirement.
This exchange requirement allows for the provision of information at various stages during the design process including outline conceptual or sketch design, full conceptual design and coordinated design. The information provided at each stage is essentially the same. However, the level of certainty regarding equipment and components used will increase at each stage allowing greater certainty in space provision.
It is assumed that the information provisions outlined in the exchange requirement er_exchange_HVAC_model (space) have been satisfied. This provides an initial assessment of spaces from the perspective of building design and HVAC design as well as project details.
Information provided through this exchange requirement includes:
- HVAC component type and size
- Required electrical connection load and control/starting method
- Required piping connection loads for each service type
- Required control system interfaces and system logic
- Shape representation of component (using an appropriate representation form that may be symbolic, 2D, 3D boundary representation etc.); the form of representation to be used and the extent of detail that is provided for the component may differ at different stages of the project.
- Weight (and optionally center of gravity) of component type
- Location and orientation of occurrences of component type
The requirement to specify duct networks would not normally be required, but may be necessary where the imposed load of the ductwork exceeds normal structural design criteria, for example fire rated ductwork constructed of heavy guage materials.
Information Requirements
| Context | Description | Man | Rec | Opt | Actor Supplying | Functional Part |
|---|---|---|---|---|---|---|
| Precursor | The provisions of the exchange requirement er_exchange_HVAC_model(space) must be satisfied. This includes:
|
|
HVAC Design | er_exchange_HVAC_model(space) | ||
| Precursor | The provisions of the exchange requirement er_exchange_structural_model must be satisfied so that the shape, size and location of structural members are available for reference and coordination. | |
Structural Design | er_exchange_structural_model | ||
| Owner History | The owner history of the equipment must be asserted. | HVAC Design | fp_model_HVAC_equipment (type, predefined_type) | |||
| General Attributes | For each item of HVAC equipment to be considered, general attributes of the equipment types and occurrences may be specified including:
|
HVAC Design | fp_model_HVAC_equipment (type, predefined_type) | |||
| Placement and Shape | The shape representation and placement for the HVAC equipment should be asserted. The shape representation of an item of HVAC equipment is typically a representation map which is defined for the equipment type and then referenced for each occurrence. Each occurrence specifies its own placement. Within the representation map, the particular form of the shape representation may differ according to the life cycle stage as with flow segments. Generally, the representations selected for the flow fitting representation map will follow the representations selected for flow segments. Note that since IFC generally allows for elements to have multiple shape representations, provision of shape representations of HVAC systems at different lifecycle stages should be considered as cumulative and not as alternative. Representations may be either:
|
HVAC Design | fp_model_HVAC_equipment (type, predefined_type) | |||
| Equipment Weight | As well as the placement and shape of components, the weight of major items needs to be captured and communicated to ensure structural coordination | HVAC Design | fp_define_quantity |
Results
| Type | Information Requirements | Actor Receiving | |
|---|---|---|---|
| Model | Building model updated for component information providing information to the Building Designer. Shape and location of components may have been provided previously or may be specified through this exchange requirement. |
|
|
| Model | Building model updated for component information providing information to the Electrical Designer. Electrical requirements of components may have been provided previously or may be specified through this exchange requirement. |
|
|
| Model | Building model updated for component information providing information to the Piping Designer. Piped Services requirements of components may have been provided previously or may be specified through this exchange requirement. |
|
|
| Model | Building model updated for component information providing information to the Controls Designer. Control requirements of components may have been provided previously or may be specified through this exchange requirement. |
|
|
| Model | Building model updated for component information providing information to the Structural Designer. Shape and location of components may have been provided previously or may be specified through this exchange requirement. |
|
Referenced by
This list shows all process maps which reference this specific ER.
|
Labels: pm, er-exchange-hvac-model-equipment, er-exchange-hvac-model-systems |
|
Labels: pm, er-exchange-hvac-model-equipment |
|
Labels: pm, er-exchange-hvac-model-equipment |
|
Labels: pm, er-exchange-hvac-model-equipment |
|
Labels: pm, er-exchange-hvac-model-equipment |