Log In   View a printable version of the current page.
Maximum Internal Heat Gain (FP)
Added by Janice Wix, last edited by Janice Wix on Jan 30, 2007  (view change)
Labels: 
(None)


Maximum Internal Heat Gain

Overview

Specifies the quantities that enable the calculation of internal heat gains for a space. The total value of internal heat gains should be the gain occurring at the time of maximum heat gain to the space taking into account solar, infiltration and internal gains. It is not necessarily the maximum actual internal heat gain into a space which may occur at a time when solar and infiltration components of the total gain are lower.
Internal heat gains include:

  • sensible and latent heat gains from space occupants,
  • sensible and latent heat gains from equipment and machinery,
  • sensible heat gains from lights.

Results

xxx

Description Entity/Pset MAN REC OPT
The space for which the boundaries are to be determined must be identified. IfcSpace      
PEOPLE        
Specify that gains are from people. The value of the thermal load source should be set to .PEOPLE. IfcSpaceThermalLoadProperties.ThermalLoadSource
IfcPropertyEnumeratedValue
IfcThermalLoadSourceEnum
     
Specify the stage at which the values are to be determined. For design stage calculations, the value should be set to .DESIGN. or .DESIGNMAXIMUM. IfcSpaceThermalLoadProperties.PropertySource
IfcPropertyEnumeratedValue
IfcPropertySourceEnum
     
Specify the activity for which people (metabolic) gains are being determined. Note that activities may be specified differently in different places. Pset_SpaceOccupancyRequirements.OccupancyType
IfcPropertySingleValue
IfcLabel
     
Specify the number of people carrying out each activity within the space at the point of maximum heat gain Pset_SpaceOccupancyRequirements.OccupancyNumber
IfcPropertySingleValue
IfcCountMeasure
     
OPTIONALLY: Specify the gain type concerned. If this is for a sensible gain, the value will be .SENSIBLE. If for a latent gain, the value will be .LATENT. IfcSpaceThermalLoadProperties.ThermalLoadType
IfcThermalLoadTypeEnum
     
OPTIONALLY: Specify the value of the gain per person IfcSpaceThermalLoadProperties.MaximumValue
IfcPowerMeasure
     
EQUIPMENT        
Specify that gains are from equipment. The value of the thermal load source should be set to .EQUIPMENTSENSIBLE. IfcSpaceThermalLoadProperties.ThermalLoadSourceIfcPropertyEnumeratedValue
IfcThermalLoadSourceEnum
     
Specify the stage at which the values are to be determined. For design stage calculations, the value should be set to .DESIGN. or .DESIGNMAXIMUM. IfcSpaceThermalLoadProperties.PropertySource
IfcPropertyEnumeratedValue
IfcPropertySourceEnum
     
Identify the equipment (gas and electric) within a space that contribute to heat gains
 
The relating structure is the space of interest
 
The related elements contained in the spatial structure are flow terminals that are defined as being either electrical appliances or gas terminals.
 
The relating type for the type definition is an electrical appliance or a gas terminal
 
The related objects in the type definition are those occurrences of flow terminal that are typed as being light fixtures
IfcRelContainedInSpatialStructure.RelatingStructure
IfcSpace
 
IfcRelContainedInSpatialStructure.RelatedElements
IfcFlowTerminal
 
IfcRelDefinesByType.RelatingType
IfcTypeProduct
IfcElectricalApplianceType
IfcGasTerminalType
 
IfcRelDefinesByType.RelatedObjects
IfcFlowTerminal
     
OPTIONALLY: Specify the gain type concerned. If this is for a sensible gain, the value will be .SENSIBLE. If for a latent gain, the value will be .LATENT. IfcSpaceThermalLoadProperties.ThermalLoadType
IfcThermalLoadTypeEnum
     
OPTIONALLY: Specify the value of the gain per item of equipment IfcSpaceThermalLoadProperties.MaximumValue
IfcPowerMeasure
     
LIGHTING        
Specify that gains are from lighting. The value of the thermal load source should be set to .LIGHTING. IfcSpaceThermalLoadProperties.ThermalLoadSourceIfcPropertyEnumeratedValue
IfcThermalLoadSourceEnum
     
Specify the stage at which the values are to be determined. For design stage calculations, the value should be set to .DESIGN. or .DESIGNMAXIMUM. IfcSpaceThermalLoadProperties.PropertySource
IfcPropertyEnumeratedValue
IfcPropertySourceEnum
     
Identify the lights within a space that conform to a particular light fixture type
 
The relating structure is the space of interest
 
The related elements contained in the spatial structure are flow terminals that are defined as being light fixtures.
 
The relating type for the type definition is a light fixture
 
The related objects in the type definition are those occurrences of flow terminal that are typed as being light fixtures
IfcRelContainedInSpatialStructure.RelatingStructure
IfcSpace
 
IfcRelContainedInSpatialStructure.RelatedElements
IfcFlowTerminal
 
IfcRelDefinesByType.RelatingType
IfcTypeProduct
IfcLightFixtureType
 
IfcRelDefinesByType.RelatedObjects
IfcFlowTerminal
     
Identify the sensible heat gain from the light fixture type used. IfcLightFixtureType
Pset_LightFixtureTypeCommon.TotalWattage IfcPowerMeasure
     
OPTIONALLY: Specify the gain type concerned. This will be only .SENSIBLE. for lighting heat gains. IfcSpaceThermalLoadProperties.ThermalLoadType
IfcThermalLoadTypeEnum
     
OPTIONALLY: Specify the value of the gain per light fixture IfcSpaceThermalLoadProperties.MaximumValue
IfcPowerMeasure
     

Powered by Atlassian Confluence, the Enterprise Wiki. (Version: 2.1.3 Build:#408 Jan 23, 2006) - Bug/feature request - Contact Administrators